Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02665
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/10/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
06/10/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide a complete plumbing plan. |
06/10/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
06/10/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/10/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
06/10/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
06/14/2005 | JMORALE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
06/14/2005 | JMORALE1 | WWM | REVIEW | Needs Review | |
06/14/2005 | JMORALE1 | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM02665 DENIED 6/10/05 1. Provide power requirements for new Water Heater on Plumbing Plans. 2. There is one receptacle on Sheet E1.1 without power on panel schedule. 3. Correct Ckts on Panel A, 14, 16, 18, 20, & 22. Load calcs new review. |