Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02618
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/08/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
06/08/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the pipe sizes for the waste piping for the new fixtures. 2. Relocate the cleanout for the water closet to provide access. Reference Sections 707.9 and 707.10, UPC 1994. 3. The minimum font size for all drawings is 10 points. |
06/08/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CLARIFY FIXTURE FLOOR CLEARANCES PER ANSI A117.1 2003 STANDARDS. 2) PROVIDE CODE ANALYSIS CLARIFYING SEPARATED / NON-SEPARATED USE. |
06/08/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
06/08/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Specify lighting fisture. |
06/08/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the space complies with the ventilation requirements of Section 403.3, IMC 2000. |
06/14/2005 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
06/14/2005 | CAGUILA1 | WWM | REVIEW | Needs Review | |
06/14/2005 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/14/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |