Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM02618
Parcel: 133369570

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02618
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2005 JIM EGAN FIRE REVIEW Approved
06/08/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the pipe sizes for the waste piping for the new fixtures.
2. Relocate the cleanout for the water closet to provide access. Reference Sections 707.9 and 707.10, UPC 1994.
3. The minimum font size for all drawings is 10 points.
06/08/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY FIXTURE FLOOR CLEARANCES PER ANSI A117.1 2003 STANDARDS.
2) PROVIDE CODE ANALYSIS CLARIFYING SEPARATED / NON-SEPARATED USE.
06/08/2005 ROBERT SHERRY WATER REVIEW Approved
06/08/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved Specify lighting fisture.
06/08/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the space complies with the ventilation requirements of Section 403.3, IMC 2000.
06/14/2005 CAGUILA1 ZONING REVIEW Needs Review
06/14/2005 CAGUILA1 WWM REVIEW Needs Review
06/14/2005 CAGUILA1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/14/2005 CINDY AGUILAR OUT TO CUSTOMER Completed