Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T05CM02614
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | Need to provide evidence of permit for septic an/or a new septic design. No permit record can be found. RSF |
| 07/08/2005 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Approved | PLAN CHECK COMMENTS - PROJECT #T05CM02614 7/12/05 320 E. ARAGON RD. #2 PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. STRUCTURAL PLANS: 1. PLEASE UPDATE THE NOTES TO THE 2003 I.R.C. SECTIONS - DETAILS - MISC. NOTES: 1. PROVIDE A CROSS SECTION OF A TYPICAL INTERIOR PARTITION ; WOOD AND THE OPTIONAL METAL STUDS. 2. PROVIDE THE PRIOR PERMIT INSPECTIONS FOR THE WALLS, FOUNDATION, PLUMBING, ETC. PLUMBING PLANS: 1. THE WATER DEMAND LOAD FOR A CLOTHES WASHER IS 6 FIXTURE UNITS. 2. GAS NOTE 1 / 8 ; PLEASE REFER TO THE '94 U.P.C. WITH STATE AMENDMENTS. ELECTRICAL PLAN: 1. PLEASE PROVIDE ARC FAULT PROTECTION FOR THE BEDROOM RECEPTACLES. 2. HOW DO THE EXTERIOR LIGHT FIXTURES COMPLY WITH THE OUTDOOR LIGHTING CODE ? IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/12/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |