Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM02599
Parcel: 110060760

Review Status: Completed

Review Details: REVISION - SITE

Permit Number - T05CM02599
Review Name: REVISION - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2007 TERRY STEVENS ZONING REVIEW Approved
04/05/2007 DROBEY1 LANDSCAPE REVIEW Needs Review
04/05/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review Tucson Water does not provide any 3/4" water meters and the 5/8" meters are limited to 10 GPM demand. Revise the meter sizes to 1" to accomodate the demand of 20 GPM (29.5 fixture units).

Final Status

Task End Date Reviewer's Name Type of Review Description
04/05/2007 DELMA ROBEY OUT TO CUSTOMER Completed