Permit Number: T05CM02567
Parcel: 11611003H

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T05CM02567
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/07/2005 JIM EGAN FIRE REVIEW Denied 1. Fire hydrants required. Submit approved COT Water Plan.
2. Provide complete fire sprinkler system design criteria for Apartment Buildings on plans. Indicate fire sprinklers required for dwelling unit porches (balconies) per 2003 IBC and 2003 IFC Sec. 903.3.1.2.1.
3. Show location for sprinkler riser for each Apartment Building on plan. Must be protected from weather. Must be accessible to property management at all times for required maintenace, repairs and emergency operation.
09/06/2005 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Approved
09/09/2005 CAGUILA1 ENGINEERING REVIEW Needs Review
09/09/2005 CAGUILA1 WWM REVIEW Needs Review
09/09/2005 CAGUILA1 ZONING REVIEW Needs Review
09/09/2005 CAGUILA1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed
09/09/2005 CAGUILA1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2005 CINDY AGUILAR OUT TO CUSTOMER Completed