Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T05CM02534
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/19/2005 | JIM EGAN | FIRE | REVIEW | Denied | 1. Fire hydrants required. Submit approved COT Water Plan. |
07/20/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | will not review until addressing is resolved with Pima Co addressing 740-6480 |
07/25/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/26/2005 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: Frank Mendoza DATE: July 26, 2005 SBBL, Architects 1001 N. Alvernon Way Tucson, Arizona 85711 SUBJECT:Rita Houghton Retail Center,8210 S.Houghton Rd. Building Plan T05CM02534 (First Review) T15S, R15E, Section 26 RESUBMITTAL REQUIRED: Building Plan. The Building Plan cannot be approved as submitted. Please address the following review comments prior to the next submittal. Building Plan: 1. Please include a response letter to the comments along with the corrected copies of the GP. 2. There are two different addresses associated with this project, · 8210 S. Houghton Road · 8248 S. Houghton Road One site administration address should be used for the entire project and as well as for the individual submittals, i.e.: Paving and Grading plans, Development plan, etc… Revise as necessary. 3. The Grading and Paving plan in the building plan set does not reflect the most recent submittal. Use the current Grading and Paving plan in the building plan set. If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson/Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 791-5550 x1193 office (520) 879-8010 fax C:/8210 S. Houghton Rd. bldg. plans |
08/04/2005 | DAN CASTRO | ZONING | REVIEW | Denied | 1. Zoning Review Section may not approve the building plans prior to complete Structural Review approval. 2. Each building plan set shall include a copy of the stamped approved development plan/site plan. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/08/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |