Permit Number: T05CM02511
Parcel: 11615194B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02511
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Load calculations for SES-1 and SES-2 totals 151A. Existing service entrance conductors have been documented by the Registrant as 1/0 Cu, of ampacity 150A according to NEC Table 310.16. Also note that SES-2 does not include load for Owner's Panel. This needs to be resolved.
2. Load calculations for SES-3 total 222A. Existing service entrance conductors have been documented by the Registrant as 3/0 Cu, of ampacity 200A according to NEC Table 310.16. This needs to be resolved.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/19/2005 JMORALE1 OUT TO CUSTOMER Completed
09/19/2005 SUE REEVES REJECT SHELF Completed