Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM02511
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Load calculations for SES-1 and SES-2 totals 151A. Existing service entrance conductors have been documented by the Registrant as 1/0 Cu, of ampacity 150A according to NEC Table 310.16. Also note that SES-2 does not include load for Owner's Panel. This needs to be resolved. 2. Load calculations for SES-3 total 222A. Existing service entrance conductors have been documented by the Registrant as 3/0 Cu, of ampacity 200A according to NEC Table 310.16. This needs to be resolved. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/19/2005 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 09/19/2005 | SUE REEVES | REJECT SHELF | Completed |