Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM02507
Parcel: 11615194B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02507
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Load calculations for SES-1 and SES-3 total 152A. Existing service entrance conductors have been documented by the Registrant as 1/0 Cu, of ampacity 150A according to NEC Table 310.16. This needs to be resolved.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/19/2005 JMORALE1 OUT TO CUSTOMER Completed
09/19/2005 SUE REEVES REJECT SHELF Completed