Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM02507
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/23/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. It is permissible to use the calculation permitted by NEC 220.32, if each dwelling unit is equipped with electric cooking equipment. No such equipment is indicated on the plans. The Exception allows this Optional Calculation to be used, only if 8 KW is added per unit. 2. Current version of the plans deleted the feeder load calculation, and refers us to the service load calculation. Feeder load calculation is still necessary. 3. The Owner's Panel added to SES-2 may not have the demand factor applied. This entire load shall be added after the multi-family load for the 3 dwelling units has been calculated. 4. Sheet E-1 documents 2/0 Service Entrance Conductors, typical. Ampacity 175A per NEC Table 310.16. Sheet E-2 documents SES-2 as 150A. Coordinate sheets and clarify. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/31/2005 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/31/2005 | SUE REEVES | REJECT SHELF | Completed |