Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2005 JIM EGAN FIRE REVIEW Passed
07/21/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM02507 7/21/05

1. Show how 30.8 KVA was arrived at for SES 1. (12333) (4) = 49,332 VA. That's 206A. 2/0 is rated for 175A.
2. For SES 2 demonstrate that the 2-bedroom unit not in this scope of work is only 3067 KVA. 15400 - 12333 = 3067.
3. Load Calculations for SES-2 load calculations account for 3 panels. There are 4 panels on this service according to the line diagram.
4. Show how 30.8 KVA was arrived at for SES 3. (12333) (4) = 49,332 VA. That's 206A. 2/0 is rated for 175A.
08/22/2005 GERRY KOZIOL WWM REVIEW Approved