Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM02507
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2005 | JIM EGAN | FIRE | REVIEW | Passed | |
| 07/21/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM02507 7/21/05 1. Show how 30.8 KVA was arrived at for SES 1. (12333) (4) = 49,332 VA. That's 206A. 2/0 is rated for 175A. 2. For SES 2 demonstrate that the 2-bedroom unit not in this scope of work is only 3067 KVA. 15400 - 12333 = 3067. 3. Load Calculations for SES-2 load calculations account for 3 panels. There are 4 panels on this service according to the line diagram. 4. Show how 30.8 KVA was arrived at for SES 3. (12333) (4) = 49,332 VA. That's 206A. 2/0 is rated for 175A. |
| 08/22/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |