Permit Number: T05CM02507
Parcel: 11615194B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02507
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
07/19/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/19/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
07/19/2005 ROBERT SHERRY WATER REVIEW Approved
07/19/2005 PETER MCLAUGHLIN ZONING REVIEW Approved
07/19/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/19/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM02507 7/19/05

1. Remove redundant load calculation. Panel schedules already have load tabulation.
2. General Notes 5 and 8 refer to IRC. IRC only applies to single family dwellings and duplexes. For triplex and larger use NEC 2002.
3. Account for largest motor on 1-bedroom panel.
4. Indicate sizes of panels on line diagram, or provide for typical description.
07/21/2005 CAGUILA1 WWM REVIEW Needs Review
07/21/2005 CAGUILA1 FIRE REVIEW Needs Review