Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02507
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 07/19/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/19/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/19/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/19/2005 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 07/19/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 07/19/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM02507 7/19/05 1. Remove redundant load calculation. Panel schedules already have load tabulation. 2. General Notes 5 and 8 refer to IRC. IRC only applies to single family dwellings and duplexes. For triplex and larger use NEC 2002. 3. Account for largest motor on 1-bedroom panel. 4. Indicate sizes of panels on line diagram, or provide for typical description. |
| 07/21/2005 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 07/21/2005 | CAGUILA1 | FIRE | REVIEW | Needs Review |