Permit Number: T05CM02507
Parcel: 11615194B

Review Status: Completed

Review Details: REVISION - - 5TH

Permit Number - T05CM02507
Review Name: REVISION - - 5TH
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM02507 2/25/06

Revised panel schedules and load calculations OK.

1. SES 1, SES2, AND SES3 on BLDG 7 HAVE NEW 1/0 Cu service entrance conductors. Ampacity 150A per NEC Table 310.16 75 C column. SES1 draws 158A, and SES3 draws 157A. Make corrections on this Building and all others which may apply.
2. Provide TEP available fault current for services which have 2/0 and 4/0 service entrance conductors.
3. SES3 on Building 8 has arrowheads indicating both 1/0, and 4/0 service entrance conductors. Please clarify in this case, and all others which may apply.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/27/2006 GBONILL1 OUT TO CUSTOMER Completed