Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 5TH
Permit Number - T05CM02507
Review Name: REVISION - - 5TH
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM02507 2/25/06 Revised panel schedules and load calculations OK. 1. SES 1, SES2, AND SES3 on BLDG 7 HAVE NEW 1/0 Cu service entrance conductors. Ampacity 150A per NEC Table 310.16 75 C column. SES1 draws 158A, and SES3 draws 157A. Make corrections on this Building and all others which may apply. 2. Provide TEP available fault current for services which have 2/0 and 4/0 service entrance conductors. 3. SES3 on Building 8 has arrowheads indicating both 1/0, and 4/0 service entrance conductors. Please clarify in this case, and all others which may apply. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/27/2006 | GBONILL1 | OUT TO CUSTOMER | Completed |