| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/23/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM02507 2/23/06 Revised panel schedules OK. Re-compute 220.32 calculations per discussion at counter, (4) 2BR units on BLDG 1 SES-1 (2112 + 1200) (4) = 13248, not 8448. Typical. Reference NEC 220.32 (C) (3). |