Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02502
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2005 | JIM EGAN | FIRE | REVIEW | Completed | |
| 06/29/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide upper terminal cleanouts for the clotheswasher and for the bathtub. 2. Relocate the water heater. Reference Section 509, UPC 1994. 3. Provide a riser diagram for the water piping. 4. Resize the main gas line using Table 12-3, UPC 1994. 5. Clarify the recirculation of the hot water. |
| 06/29/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | |
| 06/29/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/29/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Confirm the size of the flue for the water heater. 2. Provide listing information for the ventless dryer. |
| 06/30/2005 | GBONILL1 | ZONING | REVIEW | Needs Review | |
| 06/30/2005 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 06/30/2005 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 06/30/2005 | GBONILL1 | ENGINEERING | REVIEW | Needs Review |