Permit Number: T05CM02502
Parcel: 11615194B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02502
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2005 JIM EGAN FIRE REVIEW Completed
06/29/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide upper terminal cleanouts for the clotheswasher and for the bathtub.
2. Relocate the water heater. Reference Section 509, UPC 1994.
3. Provide a riser diagram for the water piping.
4. Resize the main gas line using Table 12-3, UPC 1994.
5. Clarify the recirculation of the hot water.
06/29/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied
06/29/2005 ROBERT SHERRY WATER REVIEW Approved
06/29/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Confirm the size of the flue for the water heater.
2. Provide listing information for the ventless dryer.
06/30/2005 GBONILL1 ZONING REVIEW Needs Review
06/30/2005 GBONILL1 WWM REVIEW Needs Review
06/30/2005 GBONILL1 BUILDING-COMMERCIAL REVIEW Needs Review
06/30/2005 GBONILL1 ENGINEERING REVIEW Needs Review