Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T05CM02500
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/29/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/01/2005 | JIM EGAN | FIRE | REVIEW | Denied | 1. Fire sprinkler design criteria on Sheet ME1 is incorrect for Group M occupancy. 2. Provide complete fire sprinkler system design criteria on plans: a. Standard to be used. b. Hazard Classification c. Minimum design density and area of application. d. Water Supply info: Static__psi Residual__psi Flow__gpm. |
| 08/02/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/08/2005 | ANGIE SHOFFSTALL | OUT TO CUSTOMER | Completed |
| 08/08/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |