Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/29/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/01/2005 | JIM EGAN | FIRE | REVIEW | Denied | 1. Fire sprinkler design criteria on Sheet ME1 is incorrect for Group M occupancy. 2. Provide complete fire sprinkler system design criteria on plans: a. Standard to be used. b. Hazard Classification c. Minimum design density and area of application. d. Water Supply info: Static__psi Residual__psi Flow__gpm. |
08/02/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |