Review Details: COMMERCIAL TI

Permit Number - T05CM02495
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved 1) PROVIDE JUSTIFICATION FOR NON-SEPARATED USE.
2) PROVIDE STRUCTURAL CALCULATIONS FOR LINTEL MASONRY WALL.
3)PROVIDE VALUATION.
06/03/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM02495 DENIED 6/3/05
1. Sign and Fixture S are both on Ckt 15. Sign shall have its own circuit per NEC 600.5 (A).
2. Present a letter from the Owner providing the MSDS sheets for the paint intended for the mixing operation, certifying that the paint-mixing operation will not subject the area to classification under Article 500 of the National Electrical Code.
3. Minimum font size is 1/8".
4. Please note that receptacles for show windows must be counted at 200 VA per linear feet of window per NEC 220.12 (A).
06/10/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
06/10/2005 JIM EGAN FIRE REVIEW Approved
06/10/2005 ROBERT SHERRY WATER REVIEW Approved
06/10/2005 HEATHER THRALL ZONING REVIEW Approved
06/10/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/10/2005 JOSE ORTIZ ENGINEERING REVIEW Approved
06/24/2005 GERRY KOZIOL WWM REVIEW Approved