| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/31/2005 | GLENN MOYER | ZONING-CITY HALL | REVIEW | Denied | Please add the following notes: Noise associated with the new generator shall not exceed 70 dB(A) between 7:00am and 10:00pm 62 dB(A) between 10:00pm and 7:00am at the property line. The new generator shall be for emergency use only, and shall not be used on a daily basis. |
| 09/09/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information to show that the installation of the generator conforms to the requirements of NFPA 37 with regard to the fuel supply (Sections 6.1 and 6.3) and controls and instrumentation (Chapter 9). Reference Section 915, IMC 2000. |
| 09/29/2005 | JAY HOGAN | OPERATIONS | REVIEW | Approved | |
| 10/03/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 10/3/05 ACTIVITY NUMBER: T05CM02492 PROJECT NAME: Cell Tower PROJECT ADDRESS: 7247 E. Golf Links ARCHITECT / ENGINEER: L/D Architects PROJECT REVIEWER: Christy Foreman TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) Provide structural calculations that the slab can support the generator equipment. Justify depth of footing see section 1805.2. 2) Clarify fire seperation per table 602 distance from property lines. Site plan is unclear. 3) Clarify / justify seperated or non-seperated use section 302.3.1 & 302.3.2 between existing equipment shelter or incidental use area table 302.1.1 - Emergency generator. |
| 10/04/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/05/2005 | DAN CASTRO | ZONING | REVIEW | Denied | Zoning Review section has reviewed the plans and may approve the plans after Glenn Moyer has approved them for Special Exception review compliance. Upon obtaining approval from Glenn Moyer, the plans may be reviewed at the counter by the Zoning Review section only. Please contact me at 791-5608 ext. 1180 to set an appointment. |