Permit Number: T05CM02492
Parcel: 13510150R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02492
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/08/2005 CRAIG GROSS ZONING-CITY HALL REVIEW Approved
11/08/2005 CRAIG GROSS ZONING REVIEW Approved
11/25/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 11/25/05
ACTIVITY NUMBER: T05CM02492
PROJECT NAME: Generator for cell tower
PROJECT ADDRESS: 7247 E. Golf Links
ARCHITECT / ENGINEER: L/D Architects
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Clarify fire seperation per table 602 distance from property lines and other buildings. Site plan is unclear. I reviewed arial view of site and property lines and building need to be clarified further.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/29/2005 GBONILL1 OUT TO CUSTOMER Completed
11/29/2005 SUE REEVES REJECT SHELF Completed