Permit Review Detail
Review Status: Stopped
Review Details: COMMERCIAL NEW
Permit Number - T05CM02438
Review Name: COMMERCIAL NEW
Review Status: Stopped
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2006 | EROSE1 | BUILDING-COMMERCIAL | REVIEW | Stop | |
| 05/31/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show that the roof drainage complies with the requirements of Appendix D, UPC 1994. 2. Provide cleanouts for all sinks. Reference Section 707.4, UPC 1994. |
| 05/31/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM02438 DENIED 5/31/05 1. Demonstrate compliance with 2000 IECC. 2. Demonstrate compliance with the new Lighting Ordinance, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. 3. Electrical Note 1, change "1999" to "2002" (National Electrical Code). 4. Provide AC power requirements on Mechanical Plan. Coordinate with Mechanical and clarify. 5. It appears from the Symbol Legend that the same pandant fixture being installed in the Gas room is intended for the exterior application. Please submit a cut sheet of the exterior fixture. Plans Examiner needs to determine suitability for the installed location, and needs to verify mean lumen count used in the Lighting Ordinance compliance. 6. Per panel schedule ACs draw 26 amps. If so, they would be 3120 VA per phase, 3900 for largest motor. Coordinate with Mechanical and clarify. 7. Line diagram indicates only spaces for future loads, but no existing disconnects/panels/loads on this service. Please clarify Panels A, B, and C per Load Summary. 8. Provide fault calculations for AFC at new panel. |
| 05/31/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/31/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide mechanical plan. 2. Show that the ventilation complies with Section 403.3, IMC 2000. 3. Provide special inspection for the medical gas. 4. Provide the energy code calculations. |
| 06/01/2005 | JIM EGAN | FIRE | REVIEW | Denied | Medical gas storage room shall comply with 2003 IFC Sec. 3006.2.1. |
| 06/03/2005 | TERRY STEVENS | ZONING | REVIEW | Needs Review | |
| 06/24/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | Site plan must be approved before the building plans can be approved. |
| 07/29/2005 | ANY | WWM | REVIEW | Stopped |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/29/2005 | ANY | OUT TO CUSTOMER | Stopped |