Permit Number: T05CM02396
Parcel: 11308171A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T05CM02396
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2005 GERRY KOZIOL WWM REVIEW Denied NEEDS 8TH FLOOR REVIEW. property split crossing adjacant property. does not front public sewer.
06/22/2005 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T05CM02396

6/24/05 1029 E. BLANTON DR.

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN:

1. PLEASE UPDATE THE IRC 2000 TO THE 2003 IRC AS THE CODE OF REFERENCE.

FOUNDATION PLANS:

1. PLEASE DIMENSION THE LOCATION OF THE CARPORT FOOTINGS.

STRUCTURAL PLANS:

1. THE 4X12 #1DF APPEARS TO BE INADEQUATE. PLEASE JUSTIFY.

2. SPECIFY LUMBER GRADE AND SPECIES. SPECIFY MANUFACTURER AND SERIES ON GLULAMS AND "I" JOISTS.

3. PROVIDE MANUFACTURER'S DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS.

SECTIONS - DETAILS - MISC. NOTES:

1. HOW DOES THE CEILING DRYWALL COMPLY WITH TABLE R702.3.5 FOOTNOTE D ?

2. 1 / 7 ; DESCRIBE THE ANCHOR BOLTS.

3. 1 / 7 ; PLEASE CLARIFY THE DIMENSIONS OF THE FOOTINGS.

4. 2 / 7 ; PROVIDE THE MINIMUM THICKNESS OF THE FOOTING.

5. 2 / 7 ; RETAINING WALLS OVER 4' TALL, MEASURED FROM THE BOTTOM OF THE FOOTING, REQUIRE AN ENGINEER'S DESIGN. IS THE RETAINING WALL GOING TO BE THIS TALL? WOULD YOU CONSIDER A RESTRAINING WALL?

6. 2 / 7 ; PLEASE SPECIFY THE SIZE OF THE ANCHOR BOLTS.

7. 4 / 7 ; PLEASE SUBMIT A SPECIAL INSPECTOR FORM FOR THE USE OF EPOXY WITH THE PBV6.

8. 6 / 7 ; ER-3984 DOESN'T APPLY TO THIS TYPE ROOF.

9. 7, 8, 9, 1O, 15 / 7 ; PLEASE SPECIFY SAG-RESISTANT DRYWALL ON CEILINGS THAT ARE FRAMED AT 24" OC. SEE TABLE R702.3.5 FOOTNOTE D .

10. 13 / 7 ; PLEASE PROVIDE FIRE BLOCKS AT THE CEILING LINE.

PLUMBING PLANS:

1. THE WATER CALCULATIONS LISTS THE CLOTHES WASHER AT 2 FIXTURE UNITS WHICH CONFLICTS WITH UPC TABLE 6-3'S LISTING AT 6 FIXTURE UNITS. ALSO, PLEASE RE-COUNT THE HOSE BIBS. THE WATER LINES APPEAR TO BE UNDER SIZED.

2. THE GAS NOTES CITE IRC SECTIONS OF THE CODE. PLEASE CITE UPC SECTIONS.

3. GAS BTU DEMAND LOADS / 9 ; WHAT IS THE DIFFERENCE BETWEEN "BTU's PER HOUR" AND "TOTAL BTU's"? PLEASE PROVIDE THE INPUT RATES OF THE APPLIANCES.

4. PLEASE SIZE THE GAS LINE TO THE HEATING SECTION OF THE MECHANICAL UNIT.

5. THE SIZES ON THE ISOMETRIC DRAWING AREN'T LEGIBLE. PLEASE ENLARGE.

6. ELIMINATE THE FLAT VENTS ON THE ISOMETRIC.

7. PLUMBING NOTE 6 / 9 ; T & P LINES AREN'T PERMITTED TO TERMINATE LOWER THAN 6" ABOVE GROUND. SEE UPC 608.5 .

8. COMBUSTION AIR IS REQUIRED TO BE TAKEN FROM THE OUTSIDE. SEE THE UPC AMENDMENTS (STATE PLBG. CODE) TABLE A IN CHAPTER 5 .

MECHANICAL PLANS:

1. DO YOU NEED A DUCT UNDER THE SLAB FOR THE VENTED RANGE?


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110

Final Status

Task End Date Reviewer's Name Type of Review Description
06/29/2005 KMEDINA1 OUT TO CUSTOMER Completed