Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM02381
Parcel: 13216600A

Address:
4004 S PARK AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02381
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The information provided for the generator does not indicate that a manual leak test valve has been provided in the gas train as required by NFPA 37 (Section 5.2). Reference Section 915, IMC 2000.
2. When the generator was changed from diesel to propane, the electrical site plan was not revised to that shown on sheet A-1. Coordinate the plans. Reference Section 106.3.1, IMC 2000.
11/07/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/08/2005 CRAIG GROSS ZONING REVIEW Approved
11/08/2005 JIM EGAN FIRE REVIEW Denied Installation of LPG Storage tank requires separate plan submittals and permit. Indicate, on plan, that all references for LPG Tank installation are for information only and not a part of this approval.
11/08/2005 CRAIG GROSS ZONING-CITY HALL REVIEW Approved
11/25/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Passed
11/25/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 11/25/05
ACTIVITY NUMBER: T05CM02381
PROJECT NAME: Cell Tower
PROJECT ADDRESS: 4004 S. Park
ARCHITECT / ENGINEER: L/D Architects
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Clarify property lines, buildings, equipment, and dimensions on site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/29/2005 GBONILL1 OUT TO CUSTOMER Completed
11/29/2005 SUE REEVES REJECT SHELF Completed