| 11/17/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/30/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM02347/8 11/17/05 1. If the fuse at the AC disconnect is intended to provide overload protection, it may have to be sized smaller. (18) (1.25) = 22.5. OR (18) (1.4) = 25.2 If aanufacturer recommends a 35 AF for this unit, disregard. 2. Provide a circuit for the track lighting. 3. Provide size of electric service and service entrance conductors. 4. In Electrical Specifications, please change the wording "2000 INTERNATIONAL RESIDENTIAL CODE" to read "2002 NATIONAL ELECTRICAL CODE." |