Permit Number: T05CM02302
Parcel: 14115008V

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02302
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2005 JIM EGAN FIRE REVIEW Approved
05/20/2005 DAVE MANN PLUMBING-COMMERCIAL REVIEW Passed
05/20/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
05/20/2005 DAVE MANN MECHANICAL-COMMERCIAL REVIEW Approved
05/20/2005 TERRY STEVENS ZONING REVIEW Approved
05/20/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/23/2005 GERRY KOZIOL WWM REVIEW Passed
05/23/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM02302 DENIED 5/22/05

1. Demonstrate compliance with the 2000 IECC.
2. On Sheet E1.0, Specifications 1.2.1 note that City of Tucson enforces the 2002 NEC, not the 1999.
3. Minimum font size is 1/8". Enlarge as applicable.
05/23/2005 WATER WATER REVIEW Passed