Permit Number: T05CM02246
Parcel: 10825007D

Address:
2010 E RIVER RD

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T05CM02246
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2005 LOREN MAKUS ENGINEERING REVIEW Approved
06/16/2005 ROBERT SHERRY WATER REVIEW Approved
06/16/2005 JIM EGAN FIRE REVIEW Denied 1. Submit water plans indication location of underground fire sprinkler piping.
2. Indicate location of fire sprinkler risers. Riser must be located where protected from weather elements. Location must be accessible to property management at all times.
3. Provide complete fire sprinkler system design criteria on plans.
06/30/2005 DAVID RIVERA ZONING REVIEW Approved
06/30/2005 GBONILL1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/30/2005 GBONILL1 OUT TO CUSTOMER Completed