Permit Number: T05CM02241
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02241
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
05/20/2005 JORTIZ3 ENGINEERING REVIEW Approved
05/24/2005 JIM EGAN FIRE REVIEW Approved
05/25/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/25/2005 JMORALE1 WWM REVIEW Passed
05/25/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved 1) PROVIDE DRINKING FOUNTAIN OR LOCATE BOTTLED WATER.
2)CORRECT CODE ANALYSIS FOR UNLIMITED.
05/25/2005 ROBERT SHERRY WATER REVIEW Approved
05/25/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information to show that air will not be recirculated from the restroom. Reference Section 403.2.1, IMC 2000.
2. Show that the outside air flow rate for the rooftop unit has been adjusted per Section 403.3.2, IMC 2000.
05/27/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved