Permit Number: T05CM02239
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02239
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2005 JIM EGAN FIRE REVIEW Approved
05/17/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/17/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
05/17/2005 ROBERT SHERRY WATER REVIEW Approved
05/17/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Specify the insulation for the new flexible duct. Reference Section 803, IECC 2000.
2. Revise the ventilation calculations to include the requirements of Section 403.3.2, MC 2000.
3. Provide balancing information for the EF-2 intakes.
4. Clarify how the breakroom will recieve its scheduled ventilation.
05/18/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
05/18/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) WORK SPACES EXCEED ALLOWED OCCUPANCY.
2) IT APPEARS LAST APPROVED TENANT WAS RETAIL, THERFORE CHANGE OF OCCUPANCY. CLARIFY/JUSTIFY RESTROOM MEETS ANSI 2003 STANDARDS OR 20% COST OF CONSTRUCTION IS BEING SPENT TOWARDS COMPLIANCE.
3) CLARIFY ON CODE ANALYSIS DATA SHEET ALLOWABLE SQ. FOOTAGE. SEPARATED USE OR NON-SEPARATED USE.
05/25/2005 JMORALE1 WWM REVIEW Needs Review
05/25/2005 JMORALE1 ZONING REVIEW Needs Review