Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02239
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/17/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/17/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/17/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/17/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Specify the insulation for the new flexible duct. Reference Section 803, IECC 2000. 2. Revise the ventilation calculations to include the requirements of Section 403.3.2, MC 2000. 3. Provide balancing information for the EF-2 intakes. 4. Clarify how the breakroom will recieve its scheduled ventilation. |
| 05/18/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 05/18/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) WORK SPACES EXCEED ALLOWED OCCUPANCY. 2) IT APPEARS LAST APPROVED TENANT WAS RETAIL, THERFORE CHANGE OF OCCUPANCY. CLARIFY/JUSTIFY RESTROOM MEETS ANSI 2003 STANDARDS OR 20% COST OF CONSTRUCTION IS BEING SPENT TOWARDS COMPLIANCE. 3) CLARIFY ON CODE ANALYSIS DATA SHEET ALLOWABLE SQ. FOOTAGE. SEPARATED USE OR NON-SEPARATED USE. |
| 05/25/2005 | JMORALE1 | WWM | REVIEW | Needs Review | |
| 05/25/2005 | JMORALE1 | ZONING | REVIEW | Needs Review |