Permit Number: T05CM02206
Parcel: 127101720

Address:
710 N ALAMO AV

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM02206
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1)Clarify roof framing and provide structural calculations for this location per the 2003 IBC.
2) Clarify what equals 1 panel on site plan per structural calculations. Area on calculations provided are different for dead load and live loads.
3) Clarify flat roof or sloped roof installation.
4) Justify / clarify wind load per the 2003 IBC.
5) Clarify spacing of installation of lag bolts.
06/14/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please clarify all equipment on layout view. On the plans there are 24 panels on the layout, but only 20 on the line diagram and other system description. Show location of J-Box, DC Disconnect, TEP Service, and Solar Meter.
2. Note 1 on Page 2 0f 3. VOC = 435V, not 4.35.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/16/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
06/16/2005 SUE REEVES REJECT SHELF Completed