| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 05/16/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/16/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/16/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) ON THIRD FLOOR AND OVER 30 OCCUPANTS NEED TWO EXITS 1/2 THE DIAGONAL APART. 2) RSTROOM FACILITIES NEED TO BE ACCESSIBLE. |
| 05/16/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/16/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 05/16/2005 | JIM EGAN | FIRE | REVIEW | Denied | Minimum two exits required per 2003 IBC Table 1018.2 exit separation per 1014.2.1. |
| 05/18/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/06/2005 | GERRY KOZIOL | WWM | REVIEW | Passed |