Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02189
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/18/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/26/2005 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 05/26/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | DATE: May 26, 2005 ACTIVITY NUMBER: T05CM02189/T05OT01254 PROJECT NAME: Tom Roof The Cleaner PROJECT ADDRESS: 40 West Fort Lowell PROJECT REVIEWER: Patricia Gilbert, Engineering Associate FLOODPLAIN USE PERMIT IS DENIED RESUBMITTAL REQUIRED: SITE PLAN, ELEVATION CERTIFICATE, FLOODPLAIN USE PERMIT APPLICATION 1. This structure was built in 1986 after the Floodplain Ordinance came in to effect. This structure should be in conformance with the Floodplain Ordinance. Submit the elevation certificate for the structure that was constructed in 1986. If this structure was built to the proper elevation the 50% rule does not apply. A copy of the elevation certificate must be included with the second plan review submittal. Please contact Patricia Gilbert if you have any questions regarding this comment, 791-5550, ext. 2206. |
| 06/06/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 06/06/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/06/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the natural ventilation calculations to coordinate with the proposed floor plan. Reference Section 1203.4.1.1, IBC 2003. 2. Provide mechanical ventilation for adjoining areas not having unobstructed openings to areas with openings to the outdoors. Reference Section 401.2, IMC 2000. 3. The minimum mechanical ventilation for a public restroom is 75 CFM per water closet or urinal. Reference Section 403.3, IMC 2000. |
| 06/08/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | .. T05CM02189 .. 40 W FORT LOWELL ROAD .. DGL .. 6/10/05 .. 1ST REVIEW .. S1. Provide copy of address slip from Pima County combining 20 W Fort Lowell Rd and 40 W Fort Lowell Rd into a single suite indicated on drawings. S2. Provide complete floor plan on drawings for this tenant space as it has been expanded to include 20 W Fort Lowell Rd and 40 W Fort Lowell Rd, show all rooms and their uses. S3. Please explain fire wall designation for interior masonry wall, as this wall is indicated as a shear wall only on original drawings for this structure. If it has been modified to become a fire wall, please clarify type of fire wall per IBC Section 7 and provide details and fire listing on the drawings. S4. Provide structural design and calculations for folding partition support structure by an Arizona Registered Structural Engineer. S5. Clarify exiting from entire tenant space, including classrooms. S6. Clarify that minimum number of required plumbing facilities are provided per IBC Table 2902.1 and men's accessible toilet facility is/are provided and designated on floor plan, per IBC Section 29. S7. Clarify use of room #104. S8. Show where 20% of this alteration is spent on accessibility per IBC Section 3409. Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111. |
| 06/15/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Overall panel calculations are acceptable for the 100A panel and feeder. However, it is not clear from the panel schedule or load calculations whether any of the separate phases is overloaded. |
| 06/21/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/13/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 07/13/2005 | SUE REEVES | REJECT SHELF | Completed |