Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM02154
Parcel: 11202034A

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T05CM02154
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2005 ROBERT SHERRY WATER REVIEW Approved
07/08/2005 GERRY KOZIOL WWM REVIEW Denied Needs manhole tap permit - 2nd floor 740-6606. Needs credit evaluation - 8th floor; Yvonne 740-6500.
07/12/2005 JIM EGAN FIRE REVIEW Denied 1. Submit APRROVED COT Water Plan. Remove "Check Valve" from fire services.
2. Fire Protection Piping diagrams incorrect. Fire sprinkler piping not permitted under floor slab.
3. Submit complete fire sprinkler system design criteria on plan:
a. Design standard to be used.
b. Hazard classification(s).
c, Minimum design densities and areas of application.
d. Water supply information: Static__psi, Residual__psi, Flow __GPM.
5. Fire alarm design per 2003 IFC Sec. 907.2.2.
6. Fire sprinkler drains and inspector's test connections shall discharge to the building exterior.
7. "Floor Control Valve Assembly " Sht. P4.01U is incorrect and not acceptable.
07/13/2005 JOSE ORTIZ ENGINEERING REVIEW Approved
08/16/2005 EGRANT1 ZONING REVIEW Needs Review