Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T05CM02154
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/06/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
07/08/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | Needs manhole tap permit - 2nd floor 740-6606. Needs credit evaluation - 8th floor; Yvonne 740-6500. |
07/12/2005 | JIM EGAN | FIRE | REVIEW | Denied | 1. Submit APRROVED COT Water Plan. Remove "Check Valve" from fire services. 2. Fire Protection Piping diagrams incorrect. Fire sprinkler piping not permitted under floor slab. 3. Submit complete fire sprinkler system design criteria on plan: a. Design standard to be used. b. Hazard classification(s). c, Minimum design densities and areas of application. d. Water supply information: Static__psi, Residual__psi, Flow __GPM. 5. Fire alarm design per 2003 IFC Sec. 907.2.2. 6. Fire sprinkler drains and inspector's test connections shall discharge to the building exterior. 7. "Floor Control Valve Assembly " Sht. P4.01U is incorrect and not acceptable. |
07/13/2005 | JOSE ORTIZ | ENGINEERING | REVIEW | Approved | |
08/16/2005 | EGRANT1 | ZONING | REVIEW | Needs Review |