Permit Number: T05CM02124
Parcel: 125122720

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T05CM02124
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2005 GERRY KOZIOL WWM REVIEW Approved
05/31/2005 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens FOR: David Rivera
Senior Planner Principal Planner

PROJECT:T05CM02124
626 N. Camino Miramonte
Additions: Bedroom/Bath/Kitchen Nook
Site Plan

Transmittal date: 2nd Review 6/23/05

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. As submitted the owner proposes an addition to the rear of the residence of a master bedroom, study and bathroom. With the existing conditions this proposed addition would bring the total "bedrooms" in the residence to six (6).

2.As per Luc Sec. 6.2.2 Definitions B
Bedroom. The term bedroom shall include all of the following.

B. Any enclosed room which has a minimum area of sixty (60) square feet and has an accessible opening to the exterior of the building in compliance with the International Building Code (IBC), whether termed a studio, family room, study, den, bonus room, or any other name, except for a living room, dining room, kitchen, and bathrooms.

As per LUC Sec. 3.5.7.1.G,and.H

G. For any new single family dwelling in the R-1 zone with five (5) bedrooms, three (3) parking spaces are required. For every bedroom over five (5), one additional space is required for each bedroom.

H. For all single family dwellings in the R-1 zone with five (5) or more bedrooms, and for all lots containing two (2) or more single family dwellings, with the second dwelling having more than one bedroom, all parking and maneuvering must be located on-site, either in a side or rear perimeter yard. The vehicular use area must be improved, which includes surfacing, striping, and provision of barriers, in conformance with Development Standard 3-05.0. Parking spaces may not be located in a vehicular use area in any front street perimeter yard.

3. As per the submitted plan the owner proposes a single car garage and a vehicular use area in front of the garage, 20' in length. The codes listed in item #2 would require a min. of four (4) parking spaces and maneuverability to be maintained on the premises with no parking in the required front street perimeter yard. A Board of Adjustment variance is required.

4. If a Board of Adjustment Variance is applied for, please note the case number, date of approval, variances granted, and conditions imposed on the site plan.


If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5608 ext. 2000.
06/09/2005 NEAL SAUNDERS BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project T05cm02124

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Floor Plans

1. Verify egress from master bedroom - 20" minimum width is required.

Structural Plans

1. 7 & 9/3 - Epoxy requires special inspection. Submit form.
2. 1, 4 & 5/5 - Dimension 6" from grade to sill plate.
3. Note sheathing of shearwalls 7, 12 and 13 on plan.
4. Specify 3-1/8 x 15 GLB strapping to 2x4 wall.
5. Callout all post caps.

Plumbing and Electrical Plan

1. Gas: Provide the length of line to each appliance, BTU demand of each appliance, size of each branch, total demand, and total developed length from meter to the most remote appliance on the system per UPC 1217.2.
2. Water line: Provide the total fixture unit demand and maximum developed length. Include size of supply line from meter to house. Table 6.3 and 6.4, 1994 UPC.
3. Note on plan compliance with the water conservation requirements. Water closets, 1.6 gallons per flush, sinks and showerheads, 3 gallons per minute.
4. Note on plans that shower and tub / shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
5. Provide convenience outlet spacing in family room per E3801.2.
6. Where ceiling fans are shown on the plans, provide a note indicating only approved outlet boxes shall be used, per E4001.6.
7. Note that light fixtures in clothes closets shall be installed in accordance with E3903.11.
8. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup.

If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2005 JMORALE1 OUT TO CUSTOMER Completed
06/17/2005 SUE REEVES REJECT SHELF Completed