Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM02113
Parcel: 116122870

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T05CM02113
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
05/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM02113 DENIED 5/11/05

1. Provide available fault current at the service.
2. Provide fault current ratings of new equipment.
3. Provide fault calculations as necessary to demonstrate that all equipment is rated for AFC.
4. Add 25% for the largest motor load on the Panel B Load Summary.
5. Specify the overcurrent protection for the Panel B feeder.
6. Demonstrate that the existing electrical service was overhead, or specify an underground service.
05/17/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
05/17/2005 CAGUILA1 ZONING REVIEW Needs Review