Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE ONLY
Permit Number - T05CM02113
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM02113 DENIED 5/11/05 1. Provide available fault current at the service. 2. Provide fault current ratings of new equipment. 3. Provide fault calculations as necessary to demonstrate that all equipment is rated for AFC. 4. Add 25% for the largest motor load on the Panel B Load Summary. 5. Specify the overcurrent protection for the Panel B feeder. 6. Demonstrate that the existing electrical service was overhead, or specify an underground service. |
| 05/11/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/17/2005 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 05/17/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved |