Permit Number: T05CM02092
Parcel: 12701005D

Review Status: Completed

Review Details: REVISION

Permit Number - T05CM02092
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the initials of the engineer on the revision dated 6/7/05.
2. Provide justification for reducing the size of the cold water pipe from 3/4" to 1/2". What is the size of the water line that the new line is being connected to and what load is it carrying.
3. Explain the change to the waste and vent pipes.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/09/2005 GBONILL1 OUT TO CUSTOMER Completed