Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2005 JIM EGAN FIRE REVIEW Approved
05/10/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/10/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
05/10/2005 ROBERT SHERRY WATER REVIEW Approved
05/10/2005 TERRY STEVENS ZONING REVIEW Approved
05/10/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/10/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM02092 DENIED 5/10/05

1. For the column totals on the panel schedule to be meaningful, they need to include existing loads. It shall be obvious that no phase is overloaded.
2. In the load calculations below the panel schedule, it appears that receptacles are 2340 VA, not 1980, and that fixed loads are 9105 VA not 8925.
3. Amps appear to be calculated wrong on load calculations below panel schedule. Even if 29218 VA were the correct figure, it would not be 35.1 A at 120/208.
4. Provide load calculations to show that Panel 15BB is not overloaded.
5. There is a new Water Heater on the Electrical Plans, but not Plumbing. Provide Plumbing plans.
05/10/2005 BLANCA ESPINO ENGINEERING REVIEW Approved