Permit Number: T05CM02091
Parcel: 20914001C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02091
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2005 JIM EGAN FIRE REVIEW Approved
05/12/2005 SREEVES1 WWM REVIEW Passed no plbg on plans
06/01/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/01/2005 ROBERT SHERRY WATER REVIEW Approved
06/01/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/06/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
06/06/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Indicate number of poles and fault current rating of ATS. Note that Specifications 16250-3 1.04 B 6 and 7 call for 4-pole transfer switches to have a switched neutral pole, but 3-pole switches to have a neutral bus and lugs; modify as applicable to the single phase generator. Generator is not grounded and bonded as for a Separately Derived System.
2. Provide AFC at ATS. Specifications 16250-2 1.04 A 4 call for transfer switch equipment to withstand the AFC shown on the drawings.
3. The GND in the conduit between the CT Can and new service disconnect consists of a redundant path.
4. Since a new disconnect is on the load side of the new transfer switch, this would serve as the new service disconnect. Reference NEC 230.82. Please relocate the Grounding Electrode conductor at the new service disconnect, and specify that the N-G bond at the existing service disconnect be removed.
5. Please provide an Overcurrent Protective Device for the feeder to MDP.
6. Keynote 2 on Sheet RE2.1 refers to New Panel ATS. Do you mean New Panel UPS?
7. Keynote 10 is on Panel Schedule CT on Sheet RE2.1, but there is no such Keynote.
8. TTB receptacle was not transferred to Panel UPS, as Keynote 5 has directed.
9. With UPS specified at 4 KVA on the input, and Specifications 16611-8 2.3 F at 92% efficiency, it is questionable whether all of the 4 KVA load (+ TTB receptacle) will be carried by this UPS. (4000) (0.92) = 3680.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
06/15/2005 SUE REEVES REJECT SHELF Completed