Review Details: COMMERCIAL TI

Permit Number - T05CM02090
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2005 JIM EGAN FIRE REVIEW Approved
05/12/2005 SREEVES1 WWM REVIEW Passed no plbg on plans
06/01/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/01/2005 ROBERT SHERRY WATER REVIEW Approved
06/01/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/06/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
06/06/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Indicate number of poles and fault current rating of ATS. Note that Specifications 16250-3 1.04 B 6 and 7 call for 4-pole transfer switches to have a switched neutral pole, but 3-pole switches to have a neutral bus and lugs. Generator is grounded and bonded as for a Separately Derived System.
2. Provide AFC at ATS. Specifications 16250-2 1.04 A 4 call for transfer switch equipment to withstand the AFC shown on the drawings.
3. The GND in the conduit between the CT Can and new service disconnect consists of a redundant path.
4. Please provide the size of the Grounding Electrode conductor at the new service disconnect.
5. Please provide a panel schedule for new Panel "EMR".

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
06/15/2005 SUE REEVES REJECT SHELF Completed