Permit Number: T05CM02085
Parcel: 133090590

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T05CM02085
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2005 ROBERT SHERRY WATER REVIEW Approved
09/15/2005 JIM EGAN FIRE REVIEW Approved 1. Provide complete fire sprinkler system design criteria on plan:
a. Design standard to be used.
b. Hazard Classification
c. Minimum design density and area of application.
d. Water supply information: Static__psi, Residual__psi, Flow__ GPM.
2. Fire sprinkler riser detail (Detail 3/P2.1) is incorrect and no acceptable.
09/16/2005 HEATHER THRALL ZONING REVIEW Approved
09/16/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/21/2005 GERRY KOZIOL WWM REVIEW Denied needs manhole tap permit- 8th floor review /5th floor permit 740-6602/740-6606.
needs wastewater/iwc review of 1 hour photo processing -Tom Tomchak 579-5771.
needs wastewater credit evaluation for demo of service station- 8th floor 740-6500-Yvonne

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2005 GBONILL1 OUT TO CUSTOMER Completed
10/11/2005 SUE REEVES REJECT SHELF Completed