Permit Number - T05CM02056
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied STRUCTURAL REVIEW COMMENTS

DATE: 7/7/06
ACTIVITY NUMBER: T05CM02056
PROJECT NAME: Thoroughbred Nisson
PROJECT ADDRESS: 5163 E. 22nd St.
ARCHITECT / ENGINEER: Fred Fischer Jr.
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.


1) Provide architectural site plan that complies with approved site plan. Missing approved site plan by zoning to verify approval of removal of site wall. Also need to verify approval of new elevated car display. On west property line a 8ft. wall is shown on site plan that would be new since demo buildings are where wall is shown, therfore provide structural calcs. and detail for 8ft. site masonry screen wall or this wall would also need to be removed.
2) Provide structural calcs and details for HVAC equipment on roof. Metal decking cannot support the load shown on mechanical drawgs. Stuctural calculations provided are not readable. Also calculations would need to show that the building framing can carry the load from the w10 x12 to the footing adequately. Also provide framing details for the new members being added.
3) Handrail shop drawings inadequate details provide all dimensions, welds, and connections. Can be provided before installation.
4) Shop drawings for structural steel need to be reviewed and approved by structural engineer. Can be provide before installation.
07/25/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the roof structure as needed to be capable of supporting the additional dead load due to the installation of the roof top units. Reference Section 302.1, IMC 2000.
2. Show the size, routing, and termination of the condensate drain for the elevator a/c unit, FC-1. Reference Section 307.2, IMC 2003 and Section 807.2, UPC 2003.
08/09/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
08/15/2006 GERRY KOZIOL WWM REVIEW Denied needs to show location/method of connection to public sewer. needs ww/iwc review & approval. (Tom Tomchak 579-5771) needs WW 8th floor credit evaluation for bldg demo.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/21/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
08/21/2006 SUE REEVES REJECT SHELF Completed