Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM02056
Parcel: 12814136A

Address:
5163 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02056
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2006 DAVE MANN FIRE REVIEW Approv-Cond Provide Fire Department Lock Box at sliding gate
(Application form rolled up with plans)
06/01/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Third request. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference Section 302.1, IMC 2000.
2. Third request. Provide information to show that the elevator machine room does not require an independent venting or air conditioning system to prevent overheating of the elevator equipment. Reference Section 3006, IBC 2003.
06/01/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Third request. Provide site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Note that the Grading/Utilities Plan (dated 12/15/05) submitted with this package indicates a "new ¾" water service" to "connect new water service to existing water line" along a 3" water line running south of the proposed building, in the abandoned alley. It also shows an existing 4" building sewer running north from the new building, approximately 85 feet west of the Northeast corner of the building. None of this even resembles the plumbing design drawings. Reference Section 103.2.3, UPC 2003.
2. Provide listing information for the reduced pressure backflow preventer upon which the water pressure calculations have been based. No reduced pressure backflow preventer information provided with the civil drawings. Note that a pressure drop of only 5 psig is highly unlikely with an approved reduced pressure backflow preventer. Reference Section 103.2.3, UPC 2003.
3. Coordinate the plumbing fixture layout (sheet P-2.0) with the fixtures shown on sheets A-2.1 and A8.1; the fixture layout in room 106 is not the same. Reference Section 103.2.3, UPC 2003.
4. Third request; see plumbing comment 1. Provide site drawing showing the size, route, and slope of the building sewer. Reference Section 103.2.3, UPC 2003.
5. Based on the provided waste and vent isometric, each fixture (e.g. floor drain) requires a vent (Sections 901.0 and 910.1, UPC 2003). Changes in pipe size downstream of an upper terminal cleanout may require an additional cleanout in order to conform to Section 707.11 (e.g. 2" to 3" pipe).
6. Clarify the nature of the devices shown on the domestic water isometric as "EWH-1"; are they actually trap primers (TP)?
7. Increasing the developed length of the natural gas piping has resulted in the natural gas line branches to RTU-1, RTU-2, RTU-3, RTU-4, RH-1, and RH-2 being undersized. The pipe segment upstream of the branch to HV-2, the main line to RH-1 and RH-2, and the line upstream of RTU-3 are undersized. The size of the branch to RTU-3 is not shown. Reference Table 12-3, UPC 2003.
8. The design of the roof drain for the entry element shown on sheet A-15.1 does not show any provision for an overflow. If an overflow is not to be installed, provide structural calculations to show that the entry element can support the weight of water that will accumulate if the primary roof drain is blocked. Reference Section 1101.11.2, UPC 1994 and Section 1611.1, IBC 2003.
9. Show how the temperature of the hot water supply to the public lavatories is controlled. The thermostat for the water heater is not an acceptable means of controlling the water temperature for this use. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
06/13/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please address motor disconnecting means for the Door Lift and Conveyer on Keynote 5 Sheet E-4. One of the j-boxes was replaced by a 30/3 disconnect w/FRN-R5 fuses, but the other one, on the opposite wall, was not modified.
2. Please provide conductor sizes for RTUs 1-4.
3. Please clarify use of Keynotes 3 and 9 on Sheet E-7. They are on the plans, but not on list of keynotes.
4. On Sheet E-4, please clarify that all equipment installed shall meet the requirements of NEC 110.26 (A) (1). Depending on the relative scale of equipment, there may not be sufficient clearance for transformer T1 in its new location.
5. Keynote 1 on Sheet E-9. This device also needs a lock-off device. Reference NEC 620.51 (A).
6. Ckts PL2-62 and PL2-66, please add the lighting to the panel schedules.
7. On Sheet E-9, it appears that PL1-68 should read "PL2-68."
8. On Sheet E-4, one of the transformers is designated "75". These are both 150s.
9. Pole height for the exterior fixtures is 30'5" on Pole Base Detail Sheet E-9. Detail sealed by the Structural Engineer specifies a maximum of 30'0".
06/13/2006 GERRY KOZIOL WWM REVIEW Denied needs to show location/method of connection to public sewer. needs ww/iwc review & approval. (Tom Tomchak 579-5771) needs WW 8th floor credit evaluation for bldg demo.
06/16/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied STRUCTURAL REVIEW COMMENTS

DATE: 6/16/06
ACTIVITY NUMBER: T05CM02056
PROJECT NAME: Thoroughbred Nisson
PROJECT ADDRESS: 5163 E. 22nd St.
ARCHITECT / ENGINEER: Fred Fischer Jr.
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.


1) Provide a accurate code analysis for occupancy and provide calculations for sq. footage increase. Clarify occupant load per room / space. section 1004.1.2 and table 1004.1.2 Clarify separated or non-separated per 302.3 mixed occupancies, 302.3.1 non-separated uses, and 302.3.2 separated uses. Per table 302.3.2 need 3 hr.separation between occupancies.

2) Provide a copy of approved site plan for reference. Last check site plan still requires revisions.

3) Clarify clear floor space for all water closets required meet ANSI A117.1 2003 standards all restrooms shown sht. A8-1. Door swing is not allowed in turning radius see section 603.2.3 see dtl 8/8.1 women's toilet. Detail 7/8.1 clear floor space per 404.2.3.1 appears water fountain is in clear floor space.

4) Design load - wind 70 mph. sht C - please justify. On response to plan check correction list. Wind loads appear to be 90 mph per figure 1609.

5) Section 1011.3 tactile exit signs? Note 19 missing @ door 101.

6) Shop drawings submitted must have reviewed & approved stamp by Architect or Engineer before submitting to City of Tucson.

7) FB-3 on diagram near elevator calls out 14 x 38 conflicts with calculations pg 36.

8) Light pole calculations justified per expired code. Justify per specified height and 2003 IBC.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/20/2006 AMERY KLAPPERT OUT TO CUSTOMER Completed
06/20/2006 SUE REEVES REJECT SHELF Completed