Permit Number: T05CM02056
Parcel: 12814136A

Address:
5163 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T05CM02056
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2005 PETER MCLAUGHLIN ZONING REVIEW Approved
12/08/2005 PETER MCLAUGHLIN ZONING HC SITE REVIEW Approved
12/09/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: December 9, 2005
ACTIVITY NUMBER: T05CM02056 Revision
PROJECT NAME: Thoroughbred Nissan
PROJECT ADDRESS: 5163 East 22nd. Street
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

1. The cut and fill quantities have not been revised from the previously approved site plan. Are the cut and fill quantities the same? Was the earthwork quantity on the previously approved plan including the revisions? Clarify in the response letter and revise the site plan as needed.

2. Submit a grading application for the revision to the site. The SWPPP must also be revised to show the site changes. Submit 3 copies of the grading and SWPPP plan with the grading application. Be advised to use the same grading plan activity number.

3. The 7000 square foot parking exclusion is an area that will not be used as a parking area and this must be clear. Indicate vertical curb between the revised employee parking lot and the 7000 square foot parking exclusion to avoid any confusion.
12/14/2005 JIM EGAN FIRE REVIEW Approved
12/16/2005 ANDREW CONNOR NPPO REVIEW Approved
12/16/2005 ANDREW CONNOR LANDSCAPE REVIEW Approved