Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM02053
Parcel: 14115008T

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02053
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2005 JIM EGAN FIRE REVIEW Approved
05/06/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the size of the existing water line connecting to the 2" main water pipe.
2. Show that the locations of the floor sinks comply with Section 804.1, UPC 1994.
05/06/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1)PROVIDE CODE ANALYSIS DATA SHT. WITH SEPERATED / NONSEPERATED USE AND MOST RESTRICTIVE OCCUPANT IN BUILDING.
05/06/2005 ROBERT SHERRY WATER REVIEW Approved
05/06/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide ventilation for the waxing and facial rooms. Reference Section 403, IMC 2000.
2. Show that the restroom ventilation complies with Sections 403.2.1 and 403.3, IMC 2000.
3. Provide balancing infomation for the exhaust grilles in the salon area.
05/09/2005 HEATHER THRALL ZONING REVIEW Approved
05/09/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CMO2053 DENIED 5/9/05

1. Provide power for RCP-1 per Sheet P2 Fixture Schedule.
2. Provide line diagram with feeder shown to Panel P6.
3. Provide service load calculations.
05/09/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
05/13/2005 CAGUILA1 WWM REVIEW Needs Review