Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02053
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/06/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/06/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show the size of the existing water line connecting to the 2" main water pipe. 2. Show that the locations of the floor sinks comply with Section 804.1, UPC 1994. |
| 05/06/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1)PROVIDE CODE ANALYSIS DATA SHT. WITH SEPERATED / NONSEPERATED USE AND MOST RESTRICTIVE OCCUPANT IN BUILDING. |
| 05/06/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/06/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide ventilation for the waxing and facial rooms. Reference Section 403, IMC 2000. 2. Show that the restroom ventilation complies with Sections 403.2.1 and 403.3, IMC 2000. 3. Provide balancing infomation for the exhaust grilles in the salon area. |
| 05/09/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 05/09/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CMO2053 DENIED 5/9/05 1. Provide power for RCP-1 per Sheet P2 Fixture Schedule. 2. Provide line diagram with feeder shown to Panel P6. 3. Provide service load calculations. |
| 05/09/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 05/13/2005 | CAGUILA1 | WWM | REVIEW | Needs Review |