Permit Number: T05CM02050
Parcel: 13408276A

Address:
8301 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02050
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2005 JIM EGAN FIRE REVIEW Approved
05/16/2005 EGRANT1 WATER REVIEW Passed
05/16/2005 EGRANT1 PLUMBING-COMMERCIAL REVIEW Passed
05/16/2005 EGRANT1 WWM REVIEW Passed
06/16/2005 ANY BUILDING-COMMERCIAL REVIEW Denied .. T05CM02050 .. 8301 E 22ND ST .. DGL .. 6/16/05 .. 1ST REVIEW ..

S1. Clarify extent of suspended ceiling, as detail #1/A2 shows a suspended ceiling in areas where exposed construction was called for on prior permit drawings, if suspended ceiling is provided in areas not previously permitted this permit must be revised to clarify locations, details and permits for this suspended ceiling.
S2. Provide occupant load calculations on the drawings.
S3. Locate/outline occupancies on floor plan.
S4. Clarify detail 1/A2 :
1. Callout connection of bracing to top plate of wall and to purlins above, specify fastener type, size, spacing/number.
2. Specify bracing ie: material type, size, strength, shape, as appropriate.
S5.Provide project valuation as affected by any revisions to this project.
S6. Address accessibility per IBC 2003 Chapter 34.
S7. Pima County Health Department approval required.



Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2005 JMORALE1 OUT TO CUSTOMER Completed
06/17/2005 JMORALE1 REJECT SHELF Completed