Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM02027
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/16/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM02027 DENIED 5/12/05 1. Provide conductor size between wireway and Panel C26. 2. Note that Demand Amps/Phase for Phase A on Panel C26 is 138.3 A at 16.6 KVA, not 69.1 A; Demand Amps/Phase for Phase B on Panel C26 is 111.7 A at 13.4 KVA, not 55.8 A. 3. Minimum font size 1/8". |
| 05/16/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/17/2005 | SEPTIC APPROVAL | WWM | REVIEW | Approved |