05/12/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/16/2005 JIM EGAN FIRE REVIEW Approved
05/16/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM02027 DENIED 5/12/05

1. Provide conductor size between wireway and Panel C26.
2. Note that Demand Amps/Phase for Phase A on Panel C26 is 138.3 A at 16.6 KVA, not 69.1 A; Demand Amps/Phase for Phase B on Panel C26 is 111.7 A at 13.4 KVA, not 55.8 A.
3. Minimum font size 1/8".
05/17/2005 SEPTIC APPROVAL WWM REVIEW Approved