Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM02027
Parcel: 20914001C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02027
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/16/2005 JIM EGAN FIRE REVIEW Approved
05/16/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM02027 DENIED 5/12/05

1. Provide conductor size between wireway and Panel C26.
2. Note that Demand Amps/Phase for Phase A on Panel C26 is 138.3 A at 16.6 KVA, not 69.1 A; Demand Amps/Phase for Phase B on Panel C26 is 111.7 A at 13.4 KVA, not 55.8 A.
3. Minimum font size 1/8".
05/17/2005 SEPTIC APPROVAL WWM REVIEW Approved