Permit Number: T05CM02027
Parcel: 20914001C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02027
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
05/05/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify how the plumbing fixture schedule and water calculations (existing) relate to the present project (i.e. the calculations call for a 1-1/4" supply but the drawing refers to a 1-1/2" supply).
2. Revise the waste piping so that the drain from the new WC and lav do not connect to the vent of the existing WC.
3. If the building sewer does not also serve other buildings on the property, revise the size of the VTR per Section 904.1, UPC 1994.
4. Revise the materials allowed for the water piping per Section 604.1, UPC 1994.
5. Provide calculations to show how the sizes of the water piping conforms to Section 610, UPC 1994.
05/05/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Passed
05/05/2005 ROBERT SHERRY WATER REVIEW Approved
05/05/2005 MICHAEL ST. PAUL ZONING REVIEW Passed
05/05/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/12/2005 JMORALE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/12/2005 JMORALE1 WWM REVIEW Needs Review
05/12/2005 JMORALE1 FIRE REVIEW Needs Review