Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM02027
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/05/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 05/05/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify how the plumbing fixture schedule and water calculations (existing) relate to the present project (i.e. the calculations call for a 1-1/4" supply but the drawing refers to a 1-1/2" supply). 2. Revise the waste piping so that the drain from the new WC and lav do not connect to the vent of the existing WC. 3. If the building sewer does not also serve other buildings on the property, revise the size of the VTR per Section 904.1, UPC 1994. 4. Revise the materials allowed for the water piping per Section 604.1, UPC 1994. 5. Provide calculations to show how the sizes of the water piping conforms to Section 610, UPC 1994. |
| 05/05/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 05/05/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/05/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
| 05/05/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 05/12/2005 | JMORALE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 05/12/2005 | JMORALE1 | WWM | REVIEW | Needs Review | |
| 05/12/2005 | JMORALE1 | FIRE | REVIEW | Needs Review |