Permit Number: T05CM02021
Parcel: 140420200

Address:
2849 E ELVIRA RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM02021
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide site plan, roof plan, and details as a set of drawings per standard submittal procedures. 8 1/2" x 11" should be copied onto plan documents for field use.
2) Jusify and provide calculations for connections at each end of the new glulam beams.
3) If existing concrete walls are tilt panels justify / clarify new loading connection does not effect existing design.is o.k.
4) Clarify transverse bracing for twisting of glulam beams.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/02/2005 DELMA ROBEY OUT TO CUSTOMER Completed