Permit Number: T05CM02015
Parcel: Unknown

Address:
7005 S PLUMER AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM02015
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2005 JIM EGAN FIRE REVIEW Approved
05/12/2005 SREEVES1 WWM REVIEW Passed no plbg on plans
06/01/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
06/01/2005 ROBERT SHERRY WATER REVIEW Approved
06/01/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
06/06/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
06/06/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Minimum font size is 1/8". Please enlarge as necessary.
2. Regarding the feeders from T1 to EDP, please clarify why 2-250 KCMIL will be spliced to 2-4/0 phase and 2-#2 N.
3. Please clarify how ATS-1, which is single phase per Keynote 16 on Sheet TE1.2, is to have 4-350 KCMIL at both sides of its terminals.
4. Indicate number of poles and fault current rating of both ATS switches. Note that Specifications 16250-3 1.04 B 6 and 7 call for 4-pole transfer switches to have a switched neutral pole, but 3-pole switches to have a neutral bus and lugs. Generator is grounded and bonded as for a Separately Derived System.
5. Provide AFC at both switches. Specifications 16250-2 1.04 A 4 call for transfer switch equipment to withstand the AFC shown on the drawings.
6. Could not find Keynote 1 on Sheet TE1.2.
7. Please clarify the intent of the load shedding arrangement, Specifications 16250-6 1.05 B 6.
8. From the way the line diagram is configured, it appears that the service disconnect is at DS-1. Please clarify why the two new 600A disconnect switches need to be service entrance rated.
9. The portion of the ATS-1 feeder between DS-1 and the fused disconnect has a 1/0 GND. This shall be 4/0 per NEC Table 250.122.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
06/15/2005 SUE REEVES REJECT SHELF Completed